How many amps a sauna heater draws
On a normal single-phase UK supply, a heater's current in amps is its power in kW × 1,000 ÷ 230. A 6kW heater is 6,000 ÷ 230 = 26.1A, twice what a 13A plug is rated for, and it keeps drawing that for the full hour the room takes to heat.
| Heater | Current at 230V | Harvia fuse, 230V single-phase | Harvia fuses, 400V three-phase | Room it suits |
|---|---|---|---|---|
| 3.5kW | 15.2A | 1 × 16A | 2 × 10A | 2–4.5m³ |
| 6kW | 26.1A | 1 × 35A | 3 × 10A | 5–8m³ |
| 8kW | 34.8A | 1 × 35A | 3 × 16A | 7–12m³ |
| 9kW | 39.1A | 1 × 50A | 3 × 16A | 8–14m³ |
The fuse and room figures are from Harvia's spec pages for its Vega heaters: 3.5kW, 6kW, 8kW and 9kW. Other makers' heaters of the same output draw the same current, because the sum depends only on power and voltage.
Three-phase wiring splits the load across 3 smaller fuses, but it only helps if your property already has a three-phase supply. If you're not sure which you have, your electrician can confirm it on the first visit.
What circuit a 3.5kW to 9kW sauna heater needs
Every electric sauna heater from 3.5kW up needs its own dedicated circuit from the consumer unit. Even the smallest draws more than the 13A a standard plug is rated for, so none of them plugs in.
Sellers quote supplies of 32A to 50A for 6kW to 9kW heaters, but the final breaker and cable are your electrician's call, made from the heater's installation instructions, the length of the run and how the cable is installed. Long runs to the bottom of the garden often need a thicker cable than a short run indoors, to keep the voltage drop within limits.
Before any of that, the electrician checks whether the house can take the extra load. That means looking at the main fuse rating and what else runs at the same time, such as an electric shower, an oven or a car charger. A 9kW heater adds about 39A on top, which an older or smaller supply may not have room for.
Heater size drives the circuit far more than brand does, so compare the supply each of the best electric sauna heaters needs before you compare their prices. Dropping from 9kW to 6kW takes about 13A off the circuit.
Part P: notifiable sauna electrical work in England
In England, regulation 12(6A) of the Building Regulations 2010 makes 3 kinds of electrical work notifiable: installing a new circuit, replacing a consumer unit, and adding to or altering circuits in a special location. The same regulation lists "a room containing a swimming pool or sauna heater" as a special location.
A sauna heater on its own circuit is therefore notifiable on 2 counts, and so is any later change to the wiring in the sauna room. A new consumer unit, if your old one has no spare way or can't take the load, is notifiable too.
A garden sauna small enough to be exempt from the Building Regulations doesn't escape this. Regulation 9 keeps Part P in force for small detached buildings that take their electricity from the house, and Approved Document P names outbuildings such as sheds and detached garages as within its scope.
| Who certifies | How it works |
|---|---|
| Registered competent person | Issues a BS 7671 certificate; the installer or its scheme sends a compliance certificate to you and building control within 30 days |
| Registered third-party certifier | Appointed before work starts by an unregistered installer, notified within 5 days of finishing, then inspects and tests |
| Building control body | Notified before work starts, decides what inspection and testing it needs, then issues a completion certificate |
In practice the first route is the simplest: hire an electrician registered with one of the government-authorised competent person schemes, and the certificate and notification come with the job.
Sauna electrics in Wales and Scotland
Wales casts the net wider. Its Approved Document P for Wales lists hot air saunas as a special location and outdoor lighting and power as a special installation, and says any new work in the garden, or that involves crossing it, is notifiable. Adding a socket to an outside wall is notifiable too, and the document notes it needs RCD protection.
So in Wales, even extending an existing circuit to a garden sauna is notifiable, where in England only a new circuit or work in the sauna room itself would be. There, a Part P registered installer issues the compliance certificate, or an unregistered one notifies building control before work starts.
Scotland has no Part P. Under regulation 5 of the Building (Scotland) Regulations 2004, work listed in schedule 3, which includes most work to or in a house, needs no building warrant but must still meet the building standards. A garden sauna with a wood-burning stove is different, because the outbuilding exemptions exclude buildings with a fixed combustion appliance.
| New sauna circuit | England | Wales | Scotland |
|---|---|---|---|
| Notifiable or warrant needed? | Yes, new circuit and special location | Yes, special location and outdoor work | No warrant for most electrical work in a house |
| Must meet BS 7671? | Yes | Yes | Must meet the building standards |
| Replacing the consumer unit | Notifiable | Notifiable | No warrant for most work in a house |
BS 7671 for saunas in plain terms
BS 7671 is the IET Wiring Regulations, the British Standard every installation is designed, installed and tested to. Approved Document P says electrical installations should follow it, and that applies to non-notifiable work as much as notifiable work.
Saunas get their own section, Section 703, because heat and moisture change the risks. It follows the international standard for rooms and cabins containing sauna heaters, which treats the whole room as the sauna, divides it into 3 temperature zones and sets extra rules for protection against electric shock. In plain terms, it controls what equipment can sit where around the heater, what it must withstand and how it's protected.
Check the heater maker's instructions on RCDs before the circuit is designed. Harvia's Vega manual tells installers not to feed the heater's power through an RCD, and the same section explains that new elements can absorb moisture in storage and transport, which shows up as leakage until the heater has been used a few times.
Lights, sockets and any outdoor wiring are a separate matter, and your electrician designs RCD protection for the whole installation. At the end you should get a BS 7671 Electrical Installation Certificate, and for notifiable work a Building Regulations compliance or completion certificate as well.
Running power to a garden sauna
The usual way to get a heater circuit to a garden building is steel wire armoured cable, known as SWA, run from the consumer unit to an isolator at the cabin. The steel armour protects the cable from spades, forks and the odd tent peg.
It goes underground in a trench, clipped along a wall or fence, or a mix of both, and the electrician sets the cable size for the full length of the run. If you're building a concrete base, lay a duct through it before the pour, so the cable comes up inside the cabin's footprint instead of across the floor of the garden sauna base.
| Part of the job | What it involves |
|---|---|
| Consumer unit | A spare way and capacity for the new circuit, or a new unit |
| Cable run | SWA sized for the heater current and the length of the run |
| Route | Trench, wall or fence fixing, and where it enters the cabin |
| At the cabin | Isolator, heater connection and any control unit |
| Testing | Inspection, tests and certificates under BS 7671 and Part P |
Plan the run before the cabin arrives. Digging a trench across a lawn is easy before a 600kg cabin and its base are sitting on the route, and much harder after.
Plug-in infrared saunas: 13A plugs and commando sockets
Infrared cabins draw far less than a traditional heater, and some are built to plug in. Clearlight's UK range shows the spread: its 2-person indoor cabin is 2,500W on a 13A UK plug, while its 3-person cabin comes without a plug and must be hard-wired by an electrician.
| Clearlight cabin | Power | Connection |
|---|---|---|
| 1-person indoor | 2,160W | 13A UK plug |
| 2-person indoor | 2,500W | 13A UK plug |
| 3-person indoor | 2,780W | Hard-wired, no plug |
| 2-person outdoor | 2,380W | 16A commando plug |
| 5-person outdoor | 3,560W | 32A commando plug |
The outdoor cabins use commando plugs, the round industrial connectors built for outdoor use, on their 2-person and 5-person models. Plug-in doesn't mean no electrician: unless you already have a matching socket outdoors, fitting a 16A or 32A commando socket means a new circuit, which is notifiable in England and Wales.
Clearlight also says that adding its accessories to the 13A cabins can change the electrical requirement, and suggests asking an electrician whether a dedicated circuit is needed. A 2,500W cabin draws about 10.9A, so it should have a socket to itself rather than share an extension lead.
What drives the cost of sauna electrics
Electricians price sauna circuits per job, and the spread between a simple one and a hard one is wide. These are the things that move it, so you can judge a quote and give the electrician what they need to price it first time.
| Cost driver | Cheaper | Dearer |
|---|---|---|
| Distance from consumer unit | Indoor sauna next to it | Cabin at the far end of the garden |
| Route | Along a wall or through an existing duct | Trench under lawn, paving or a drive |
| Consumer unit | Spare way, modern unit | No space, or an old unit that needs replacing |
| Heater size | 3.5kW or 6kW | 9kW, needing a heavier cable and a bigger breaker |
| Supply capacity | Main fuse with headroom | Main fuse upgrade needed from the network operator |
| Certification | Registered electrician self-certifies | Unregistered installer plus building control fees |
Get the heater model and its installation manual to the electrician before they quote, along with a measured distance from the consumer unit to the cabin. Those 2 things set most of the price.
Questions people ask
What size breaker does a 6kW sauna heater need?
A 6kW heater draws about 26A at 230V, so it needs its own circuit rated above that. Harvia specifies a 35A fuse for its 6kW Vega on a single-phase supply. Your electrician sets the final rating from the heater's instructions, the cable and the length of the run.
Can I plug a sauna into a normal socket?
Only an infrared cabin designed for it. Some small indoor infrared cabins, such as Clearlight's 1-person and 2-person models, come with a 13A UK plug. A traditional sauna heater of 3.5kW or more draws over 13A and must be hard-wired on its own circuit.
Do I need an electrician to install a sauna?
Yes, in practice. In England a new circuit, or work in a room containing a sauna heater, is notifiable under Part P and must be certified by a registered electrician, a registered third-party certifier or building control. Wales treats outdoor wiring and sauna work as notifiable too.
Does a sauna heater need an RCD?
It depends on the heater maker's instructions and the rest of the installation. Harvia's Vega manual says not to feed the heater through an RCD, while lights, sockets and outdoor wiring are designed with RCD protection. Your electrician decides the arrangement under BS 7671.
Is sauna electrical work different in Scotland?
Yes. Scotland has no Part P, and most electrical work in a house needs no building warrant, though it must still meet the Scottish building standards. A garden sauna with a wood-burning stove falls outside the outbuilding exemptions, so expect to need a warrant for that.